CONTROLLOGIX™ HARTANALOG MODULESCatalog Numbers: 1756sc-IF8H, 1756sc-OF8HOwner’s Guide 0300196-02 Rev. E

Strany 2

x ControlLogix™ Universal Analog Input Modules

Strany 3 - Important Notes

86 ControlLogix™ Analog HART ModulesTable 7.13 (HART Pass-Through Command Request Reply)HART pass through command request – reply packet structure Fi

Strany 4

Chapter 7: HART Channel Configuration, Data, and Status 87receiving Command 0, but for simplicity, we'll track update of thedevice information as

Strany 5 - Table of Contents

88 ControlLogix™ Analog HART ModulesTable 7.16 (HART Pass-Through Command Complete Query - Reply Packet Structure)HART pass through command complete q

Strany 6

Chapter 7: HART Channel Configuration, Data, and Status 89DEAD will be sent back if any of the following conditions are true:• Command or HART Channel

Strany 7

90 ControlLogix™ Analog HART ModulesFigure 7.10a (HART Pass-Through Request and Query Process)

Strany 8

Chapter 7: HART Channel Configuration, Data, and Status 91Figure 7.10b (HART Pass-Through Request and Query Process)

Strany 9 - Table of Contents ix

92 ControlLogix™ Analog HART ModulesFigure 7.10c (HART Pass-Through Request and Query Process)

Strany 10

Chapter 7: HART Channel Configuration, Data, and Status 93Figure 7.10d (HART Pass-Through Request and Query Process)

Strany 11

94 ControlLogix™ Analog HART ModulesFigure 7.10e (HART Pass-Through Request and Query Process)Note: The ladder in figure 7.10 can be found in the pro

Strany 12 - Should Know

Chapter 7: HART Channel Configuration, Data, and Status 95from the manufacturer code, the device type code, and the deviceidentification number. The

Strany 13 - Preface xiii

PrefaceRead this preface to familiarize yourself with the rest of the owner’sguide. This preface covers:• who should use this guide• what this guide c

Strany 14

96 ControlLogix™ Analog HART ModulesFigure 7.18 (Long Frame Address) Note: The IF8H and OF8H do not support burst mode.The 1 byte Device Type code is

Strany 15 - Chapter 1

Chapter 7: HART Channel Configuration, Data, and Status 97StatusStatus is included only in reply messages from a slave. It consists of twobytes of bi

Strany 16

98 ControlLogix™ Analog HART ModulesFigure 7.19Tag Name Value in Hex DescriptionHA RT_PA SS_THRU_REQ_TX[0] 00 HA RT channelHA RT_PA SS_THRU_REQ_TX[1]

Strany 17 - System Overview

Chapter 8: Ladder Program Examples 99Programming ExamplesProgramming ExamplesProgramming ExamplesProgramming ExamplesProgramming ExamplesEarlier chapt

Strany 18 - 4 ControlLogix

100 ControlLogix™ Analog HART ModulesFigure 8.1 (Sample Ladder Logic)Rung 0 - This rung copies the configuration data (IF8H_Config) into themodule’s c

Strany 19 - Chapter 1: Module Overview 5

Chapter 8: Ladder Program Examples 101Rung 3 - This is an optional example rung indicating how to send on-the-fly configuration data to the module. T

Strany 20 - 6 ControlLogix

102 ControlLogix™ Analog HART ModulesSet Attribute All message:Module Reconfigure Message:

Strany 21 - Power Requirements

Chapter 8: Ladder Program Examples 103Rung 4: This rung describes how to unlatch process alarms.

Strany 22 - Module Installation and

104 ControlLogix™ Analog HART ModulesDemultiplexingDemultiplexingDemultiplexingDemultiplexingDemultiplexingHART DataHART DataHART DataHART DataHART Da

Strany 23 - Under Power

Chapter 8: Ladder Program Examples 105Figure 8.3 (OF8H Demultiplexing Ladder)

Strany 24 - Directives

xii ControlLogix™ Analog HART Modules1756 Series ControlLogix Module Installation Instructions(Each module has separate document for installation) 175

Strany 25

106 ControlLogix™ Analog HART ModulesSending HARTSending HARTSending HARTSending HARTSending HARTCommandsCommandsCommandsCommandsCommandsUsing the MSG

Strany 26 - Wiring Your Module

Chapter 8: Ladder Program Examples 107Figure 8.3b (IF8H HART Message Ladder)

Strany 27 - Preparing and Wiring

108 ControlLogix™ Analog HART ModulesFigure 8.3c (IF8H HART Message Ladder)

Strany 28 - IF8H Module

Chapter 8: Ladder Program Examples 109Figure 8.3d (IF8H HART Message Ladder)

Strany 29

110 ControlLogix™ Analog HART ModulesFigure 8.3e (IF8H HART Message Ladder)

Strany 30 - OF8H Module

Chapter 8: Ladder Program Examples 111Figure 8.4a (OF8H HART Message Ladder)

Strany 31

112 ControlLogix™ Analog HART ModulesFigure 8.4b (OF8H HART Message Ladder)

Strany 32 - 18 ControlLogix

Chapter 8: Ladder Program Examples 113Figure 8.4c (OF8H HART Message Ladder)

Strany 33 - Chapter 3

114 ControlLogix™ Analog HART ModulesFigure 8.4d (OF8H HART Message Ladder)

Strany 34 - Module Operation

Chapter 8: Ladder Program Examples 115Figure 8.4e (OF8H HART Message Ladder)Swap ByteSwap ByteSwap ByteSwap ByteSwap ByteLadderLadderLadderLadderLadde

Strany 35 - Interval (RPI)

Preface xiiiare below the cut-off frequency are passed with under 3 dB of attenuationfor low-pass filters.Channel Update Time -dB (decibel) – A logari

Strany 36 - Listen-Only Mode

116 ControlLogix™ Analog HART ModulesConConConConConvvvvvererererertingtingtingtingtingUnpacUnpacUnpacUnpacUnpackkkkked ed ed ed ed ASCIIASCIIASCIIASC

Strany 37 - Input Modules

Chapter 8: Ladder Program Examples 117Figure 5.6a (Packed ASCII)

Strany 38 - Module with Multiple

118 ControlLogix™ Analog HART ModulesFigure 5.6b (Packed ASCII)

Strany 39 - Chapter 4

TTTTTrrrrroubouboubouboubleshootingleshootingleshootingleshootingleshootingUsing ModuleUsing ModuleUsing ModuleUsing ModuleUsing ModuleIndicators toIn

Strany 40 - Analog HART Modules

The following LED displays are used with ControlLogix analog HARTmodules:Using RSLogixUsing RSLogixUsing RSLogixUsing RSLogixUsing RSLogix5000 to5000

Strany 41

Chapter 9: Testing Your Module 121Fault information on the properties screen.DeterDeterDeterDeterDetermining Fmining Fmining Fmining Fmining Fault aul

Strany 42 - 28 ControlLogix

122 ControlLogix™ Analog HART Modules1756sc-IF8H Er1756sc-IF8H Er1756sc-IF8H Er1756sc-IF8H Er1756sc-IF8H Errrrrror Codesor Codesor Codesor Codesor Cod

Strany 43

Chapter 9: Testing Your Module 123Extended Fault Code Channel # Description0x002C 2 CAL BIAS SET TO NAN0x002D 2 HIGH ENGINEERING EQUAL TO LOW ENGINEER

Strany 44 - 30 ControlLogix

124 ControlLogix™ Analog HART ModulesExtended Fault Code Channel # Description0x0058 5 DIGITAL FILTER GREATER THAN TWICE THE RTS RATE0x0059 5 INVALID

Strany 45 - Overview

Chapter 9: Testing Your Module 1251756sc-OF8H Er1756sc-OF8H Er1756sc-OF8H Er1756sc-OF8H Er1756sc-OF8H Errrrrror Codesor Codesor Codesor Codesor CodesE

Strany 46 - 32 ControlLogix

xiv ControlLogix™ Analog HART ModulesStep response time – The time required for the A/D signal to reach 95%of its expected, final value, given a full-

Strany 47

126 ControlLogix™ Analog HART ModulesExtended Fault Code Channel # Description0x003A 2 BAD FAULT VALUE0x003B 2 BAD IDLE VALUE0x003C 2 SIGNAL OUT OF RA

Strany 48 - Input Tags Overview

Chapter 9: Testing Your Module 127Extended Fault Code Channel # Description0x0074 5 BAD CLAMP LATCH0x0078 5 BAD RAMP TO IDLE0x0079 5 BAD RAMP TO FAULT

Strany 49 - (OF8H Only)

128 ControlLogix™ Analog HART Modules

Strany 50 - 36 ControlLogix

Chapter 10: Maintaining Your Module And Ensuring Safety 129Maintaining Your ModuleAnd Ensuring SafetyRead this chapter to familiarize yourself with:•

Strany 51

130 ControlLogix™ HART Analog ModulesStanding Clear Of Machinery – When troubleshooting a problem withany ControlLogix system, have all personnel rema

Strany 52 - If8h0Configuration

Chapter 10: Maintaining Your Module And Ensuring Safety 131WARNINGEXPLOSION HAZARDWHEN IN HAZARDOUS LOCATIONS, TURN OFFPOWER BEFORE REPLACING OR WIRIN

Strany 53 - Table 5.1b

132 ControlLogix™ HART Analog Modules

Strany 54 - 40 ControlLogix

1756sc-IF8H Module Specifications1756sc-IF8H Module Specifications1756sc-IF8H Module Specifications1756sc-IF8H Module Specifications1756sc-IF8H Module

Strany 55 - Table 5.1d

Gain Drift with Temperature 10 ppm/°C – voltage20 ppm/°C – currentModule Error over Full Temp. Range 0.1% of range – voltage0.3% of range – currentMin

Strany 56 - 42 ControlLogix

1756sc-OF8H Module Specifications1756sc-OF8H Module Specifications1756sc-OF8H Module Specifications1756sc-OF8H Module Specifications1756sc-OF8H Module

Strany 57 - Amplitude

Module OverviewThis chapter describes the functionality of the modules and explains howthe ControlLogix controller reads/writes analog data from the m

Strany 58 - 44 ControlLogix

Module Scan Time for all Channels—Analog 12ms minimum floating pointHART (Typical) 6.4 seconds with 4 variables12 seconds with 8 variables.Isolation V

Strany 59 - Table 5.3b

PrPrPrPrProoooogggggrrrrramming amming amming amming amming YYYYYour Moduleour Moduleour Moduleour Moduleour ModuleThis chapter explains how program y

Strany 60 - 46 ControlLogix

3. After clicking “OK” you are presented with the following dialog forsetting up the general information about the module. Use the same valuesspecifi

Strany 61 - 3.) Select Monitor Tags

Appendix C: Installing the module using a Generic Module profile 139Listen-only controller connection. (Controller does not provideconfiguration but

Strany 62 - Configuration information is

140 ControlLogix™ Analog HART Modules4. Specify an RPI interval between 10.0 and 750.0 ms:

Strany 63

Appendix C: Installing the module using a Generic Module profile 141

Strany 64 - 2.) Type in the valid new

142 ControlLogix™ Analog HART Modules

Strany 65

AdAdAdAdAdditional HARditional HARditional HARditional HARditional HART PrT PrT PrT PrT Protocol Infotocol Infotocol Infotocol Infotocol Infororororor

Strany 66 - Of8h0Configuration

144 ControlLogix™ Analog HART ModulesMessageMessageMessageMessageMessageStrStrStrStrStructuructuructuructuructureeeeeThis section describes the transa

Strany 67 - Table 6.1b

Appendix D: HART Protocol Overview 145Generally, burst mode is only useful if there is just one field deviceattached to a pair of wires (since only on

Strany 68 - 54 ControlLogix

2 ControlLogix™ Analog HART ModulesInput RangesThe following tables provide compatibility information on the supportedmillivolt and voltage input and

Strany 69 - Table 6.1d

146 ControlLogix™ Analog HART ModulesUniversalUniversalUniversalUniversalUniversalCommandsCommandsCommandsCommandsCommands

Strany 70 - 56 ControlLogix

Appendix D: HART Protocol Overview 147

Strany 71 - Table 6.1f

148 ControlLogix™ Analog HART ModulesCommon PractiveCommon PractiveCommon PractiveCommon PractiveCommon PractiveCommandsCommandsCommandsCommandsComman

Strany 72 - 58 ControlLogix

Appendix D: HART Protocol Overview 149

Strany 73 - Table 6.2b

150 ControlLogix™ Analog HART Modules

Strany 74 - 60 ControlLogix

Appendix D: HART Protocol Overview 151

Strany 75 - Table 6.3

152 ControlLogix™ Analog HART ModulesStatusStatusStatusStatusStatusTwo bytes of status, also called the response code, are included in everyreply mess

Strany 76

Appendix D: HART Protocol Overview 153Table 3c (First Byte) Table 3d (Second Byte) Description Bit 0 Primary variable out of limi

Strany 77

154 ControlLogix™ Analog HART Modules

Strany 78 - Pulldown menu

Getting TechnicalAssistanceIf you need technical assistance, please review the information in Chapter9, “Testing Your Module,” before calling your loc

Strany 79

Chapter 1: Module Overview 3Diagnostic LEDsThe modules contain diagnostic LEDs that help you identify the source ofproblems that may occur during powe

Strany 80 - 66 ControlLogix

©2003, Spectrum Controls, Inc. All rights reserved. Specifications subject to change without notice. The Encompass logo andControlLogix are trademark

Strany 81

4 ControlLogix™ Analog HART ModulesModule OperationThe 1756sc-IF8H module’s input circuitry consists of eight differential-ended analog inputs, multip

Strany 82 - 68 ControlLogix

Chapter 1: Module Overview 5This page is intentionally left blank.

Strany 84 - 70 ControlLogix

6 ControlLogix™ Analog HART ModulesThis page is intentionally left blank.

Strany 85

Installing Installing Installing Installing Installing and and and and and WWWWWiring iring iring iring iring YYYYYour Moduleour Moduleour Moduleour M

Strany 86 - 72 ControlLogix

8 ControlLogix™ Analog HART ModulesUsing your module inthe ControlLogixSystemPlace your module in any slot of a ControlLogix chassis or modularexpansi

Strany 87 - Table 7.1(Packet 0)

Chapter 2: Installing And Wiring Your Module 9removed, use the write-on label located on the side of the terminal blocksto identify the modu

Strany 88 - 74 ControlLogix

10 ControlLogix™ Analog HART ModulesCompliance toEuropean UnionDirectivesIf this product bears the CE marking, it is approved for installation withint

Strany 89

Chapter 2: Installing And Wiring Your Module 11!WARNINGThese modules are to be used only with the Allen-Bradley 1756 ControlLogixSystem.To i

Strany 90 - 76 ControlLogix

12 ControlLogix™ Analog HART Modules1. Insert the U-shaped band with the longer side near the terminals. Pushthe band onto the module until it snaps i

Strany 91

Chapter 2: Installing And Wiring Your Module 13• Ground the shield drain wire at only one end of the cable. Thepreferred location is at the

Strany 92 - 78 ControlLogix

14 ControlLogix™ Analog HART Modules- connect to devices keeping the leads shortImportant: If noise persists, try grounding the opposite end of the c

Strany 93

Chapter 2: Installing And Wiring Your Module 15Current Inputs - Current inputs use the terminal block pins labelled IN+#,IN-#, and I RTN-#.

Strany 94 - Get HART Device Information

Important Notes1) PLEASE DOWNLOAD LATEST SAMPLE PROJECT FROMOUR WEBSITE AT (www.spectrumcontrols.com).2) Please read all the information in this owner

Strany 95

16 ControlLogix™ Analog HART ModulesWiring Outputs to theOF8H ModuleThe OF8H module supports voltage and current outputs.Voltage Outputs - Voltage out

Strany 96 - 82 ControlLogix

Chapter 2: Installing And Wiring Your Module 17This page intensionally left blank.

Strany 97

18 ControlLogix™ Analog HART Modules

Strany 98 - HART Pass-Through Command

Operation Within theControlLogix SystemThis chapter describes how the 1756sc-IF8H and 1756sc-OF8H analogHART modules work within the ControlLogix syst

Strany 99

RSNetWorx must be run to configure ControlNet. Follow these generalguidelines when configuring I/O modules:1. Configure all I/O modules for a given co

Strany 100 - Analog HART Modules

Chapter 3: Operation within the System 21Modules in a LocalChassisWhen a module resides in the same chassis as the owner controller, thefollowing tw

Strany 101

22 ControlLogix™ Analog HART ModulesModules in a RemoteChassisIf an input module resides in a networked chassis, the role of the RPIand the module’s R

Strany 102 - 88 ControlLogix

Chapter 3: Operation within the System 23any configuration data. In this instance, another controller owns themodule being listened to.Important: Co

Strany 103

24 ControlLogix™ Analog HART ModulesConfigurationChanges in an InputModule with MultipleOwnersYou must be careful when changing an input module’s conf

Strany 104 - 90 ControlLogix

Configuring RSLogix 5000 For The IF8Hand OF8HThis chapter explains how to incorporate your module into theControlLogix system. It also covers a brief

Strany 106 - 92 ControlLogix

26 ControlLogix™ Analog HART Modulessoftware and ladder logic. Before you can use these features you mustfirst include the module into the project.1

Strany 107

Chapter 4: Programming Your Module 27See Appendix C for more details regarding module profile settings.2. Drag and drop the IF8H or OF8H user-defined

Strany 108 - 94 ControlLogix

28 ControlLogix™ Analog HART Modulesa) Click on the data typeb) Drag it into your new project.c) Continue to drag and drop the data types until all h

Strany 109 - Slave to master 06 86

Chapter 4: Programming Your Module 29d) Paste the tags into your project. Be sure to paste the tags in the emptyfield marked with an asterisk. Refer

Strany 110 - 96 ControlLogix

30 ControlLogix™ Analog HART ModulesNote: The “Local:e:I” and “Local:e:C” tags are not copied.4. Create a new ladder logic routine in your project.

Strany 111

Chapter 4: Programming Your Module 31e) Drag and drop the routines IF8H0_Packet_Data andOF8H0_Packet_Data to the MainProgram in your project.Note: You

Strany 112 - 98 ControlLogix

32 ControlLogix™ Analog HART Modules1756sc-IF8H (If8h0Configuration)

Strany 113 - Chapter 8

Chapter 4: Programming Your Module 331756sc-OF8H (Of8h0Configuration)

Strany 114 - 100 ControlLogix

34 ControlLogix™ Analog HART ModulesInput Tags OverviewThe input tags contain the analog data, status, and HART data. As in thecase of the configura

Strany 115

Chapter 4: Programming Your Module 351756sc-OF8H (Of8hInput)Output TagsOverview(OF8H Only)The output tags are used to control the output voltage or cu

Strany 116 - Module Reconfigure Message:

Table of ContentsPreface xiWho Should Use This Guide ... xiWhat This Gu

Strany 117

36 ControlLogix™ Analog HART Modules

Strany 118 - 104 ControlLogix

Chapter 5: 1756sc-IF8H Channel Configuration, Data, and Status 37Configuration, Data,Configuration, Data,Configuration, Data,Configuration, Data,Confi

Strany 119

38 ControlLogix™ Analog HART ModulesConfigurationConfigurationConfigurationConfigurationConfigurationTTTTTaaaaags fgs fgs fgs fgs for theor theor theo

Strany 120 - 106 ControlLogix

Chapter 5: 1756sc-IF8H Channel Configuration, Data, and Status 39Table 5.1bTag Name Data Type Style DescriptionIf8h0Configuration.ChXInputRange1SINT D

Strany 121

40 ControlLogix™ Analog HART ModulesTable 5.1cTag Name Data Type Style DescriptionIf8h0Configuration.ChXHighHighAlarm1REAL FLOAT The high high process

Strany 122 - 108 ControlLogix

Chapter 5: 1756sc-IF8H Channel Configuration, Data, and Status 41Table 5.1dTag Name Data Type Style DescriptionIf8h0Configuration.ModuleConfigBits.142

Strany 123

42 ControlLogix™ Analog HART ModulesSelecting a low value (i.e. 10 Hz) for the filter frequency provides the bestnoise rejection for a channel, but it

Strany 124 - 110 ControlLogix

Chapter 5: 1756sc-IF8H Channel Configuration, Data, and Status 43TA = User specified digital filter time constant (Seconds)Xn = Current value, unfilte

Strany 125

44 ControlLogix™ Analog HART ModulesInput Input Input Input Input TTTTTaaaaagsgsgsgsgsThe following fault and status reporting and module data section

Strany 126 - 112 ControlLogix

Chapter 5: 1756sc-IF8H Channel Configuration, Data, and Status 45Table 5.3bTag Name Data Type Style DescriptionIf8h0Input.ModuleStatus.13 BOOL DEC Cha

Strany 127

vi ControlLogix™ Universal Analog Input ModulesConfiguring RSLogix5000 For The IF8Hand OF8H 25Module Installation ...

Strany 128 - 114 ControlLogix

46 ControlLogix™ Analog HART ModulesTable 5.3cTag Name Data Type Style DescriptionIf8h0Input.ChanStatus SINT[8] BIN An array of 8 SINT which display g

Strany 129

Chapter 5: 1756sc-IF8H Channel Configuration, Data, and Status 47Table 5.3dTag Name Data Type Style DescriptionIf8h0Input.CST DINT[2] DEC This is the

Strany 130 - 116 ControlLogix

48 ControlLogix™ Analog HART ModulesYou can view tags here.Click on the tag name of the data structure you want to see Configuration information is li

Strany 131 - Figure 5.6a (Packed ASCII)

Chapter 5: 1756sc-IF8H Channel Configuration, Data, and Status 49ChangingChangingChangingChangingChangingConfigurationConfigurationConfigurationConfig

Strany 132 - 118 ControlLogix

50 ControlLogix™ Analog HART Modules1.) Highlight the value of the feature you want to change 2.) Type in the valid new value.

Strany 133 - OK LED CAL LED Fault Status

Chapter 6: 1756sc-OF8H Channel Configuration, Data, and Status 51Configuration, Data,Configuration, Data,Configuration, Data,Configuration, Data,Confi

Strany 134

52 ControlLogix™ Analog HART ModulesConfigurationConfigurationConfigurationConfigurationConfigurationTTTTTaaaaags fgs fgs fgs fgs for th

Strany 135

Chapter 6: 1756sc-OF8H Channel Configuration, Data, and Status 53Table 6.1bTag Name Data Type Style DescriptionOf8h0Configuration.ChXConfigBits.21BOOL

Strany 136 - 122 ControlLogix

54 ControlLogix™ Analog HART ModulesTable 6.1cTag Name Data Type Style DescriptionOf8h0Configuration.ChXConfigBits.81BOOL DEC Hold for i

Strany 137

Chapter 6: 1756sc-OF8H Channel Configuration, Data, and Status 55Table 6.1dTag Name Data Type Style DescriptionOf8h0Configuration.ChXIdleValue1FLOAT R

Strany 138 - 124 ControlLogix

Table of Contents viiEnabling and UsingHART on the1756sc-IF8H andOF8H 67Configuring the Modules for HART ...

Strany 139

56 ControlLogix™ Analog HART ModulesTable 6.1eTag Name Data Type Style DescriptionOf8h0Configuration.HandleTimeout INT DEC There is a ha

Strany 140 - 126 ControlLogix

Chapter 6: 1756sc-OF8H Channel Configuration, Data, and Status 57Table 6.1fTag Name Data Type Style DescriptionOf8h0Configuration.ModuleConfigBits.142

Strany 141

58 ControlLogix™ Analog HART ModulesTable 6.2aTag Name Data Type Style DescriptionOf8h0Input Of8h0InputBlock NA Module input dataOf8h0In

Strany 142 - 128 ControlLogix

Chapter 6: 1756sc-OF8H Channel Configuration, Data, and Status 59Table 6.2bTag Name Data Type Style DescriptionOf8h0Input.ModuleStatus.16 BOOL DEC Cha

Strany 143 - Chapter 10

60 ControlLogix™ Analog HART ModulesTable 6.2cTag Name Data Type Style DescriptionOf8h0Input.ChanStatus SINT[8] BIN An array of 8 SINT w

Strany 144

Chapter 6: 1756sc-OF8H Channel Configuration, Data, and Status 61Table 6.2dTag Name Data Type Style DescriptionOf8h0Input.CST DINT[2] DEC This is the

Strany 145

62 ControlLogix™ Analog HART ModulesAccessing TheAccessing TheAccessing TheAccessing TheAccessing TheModule Module Module Module Module

Strany 146 - HART Analog Modules

Chapter 6: 1756sc-OF8H Channel Configuration, Data, and Status 63You can view tags here.Click on the tag name of the data structure you want to see Co

Strany 147 - Appendix A

64 ControlLogix™ Analog HART ModulesChangingChangingChangingChangingChangingConfigurationConfigurationConfigurationConfigurationConfigur

Strany 148 - Firmware Revision History

Chapter 6: 1756sc-OF8H Channel Configuration, Data, and Status 65Highlight value1.) Highlight the value of the feature you want to change 2.) Type i

Strany 149 - Appendix B

viii ControlLogix™ Universal Analog Input ModulesFigure 8.3a (IF8H HART Message Ladder)... 106F

Strany 150

66 ControlLogix™ Analog HART Modules

Strany 151

Chapter 7: HART Channel Configuration, Data, and Status 67Enabling and Using HART on theEnabling and Using HART on theEnabling and Using HART on theEn

Strany 152

68 ControlLogix™ Analog HART ModulesFigure 7.1 (Channel 0 Configuration Example)ConfConfConfConfConfiguring the OF8H Module figuring the OF8H Module f

Strany 153

Chapter 7: HART Channel Configuration, Data, and Status 69Figure 7.2 (Channel 0 Configuration Example)How theHow theHow theHow theHow theModules SendM

Strany 154 - 140 ControlLogix

70 ControlLogix™ Analog HART ModulesFigure 7.3 (Primary, Secondary and Slave connection)!Attention:Attention:Attention:Attention:Attention: Har Har

Strany 155

Chapter 7: HART Channel Configuration, Data, and Status 71Figure 7.4 (Connected and Unconnected messaging) Connected Unconnected • Analog data • Mod

Strany 156 - 142 ControlLogix

72 ControlLogix™ Analog HART ModulesFigure 7.5 (Auto Acquisition Flow)Start Channel Switch Initialized for HART? Connect to field device Read device

Strany 157 - Appendix D

Chapter 7: HART Channel Configuration, Data, and Status 73Table 7.1(Packet 0)Tag Name Data TypeStyleDescription(If8h0 or Of8h0)Packet01Packet0[8,1] NA

Strany 158 - 144 ControlLogix

74 ControlLogix™ Analog HART ModulesTable 7.2(Packet 1)Tag Name Data TypeStyleDes cription(If8h0 or Of8h0)Packet11Packet1[8,1] NA Two dimensional arra

Strany 159

Chapter 7: HART Channel Configuration, Data, and Status 75Table 7.3 (Packet 2)Tag Name Data TypeStyleDescription(If8h0 or Of8h0)Packet21Packet2[8,1] N

Strany 160 - 146 ControlLogix

Table of Contents ix

Strany 161

76 ControlLogix™ Analog HART ModulesTable 7.4 (Packet 3)Tag Name Data TypeStyleDescription(If8h0 or Of8h0)Packet31Packet3[8,1] NA Two dimensional arra

Strany 162 - 148 ControlLogix

Chapter 7: HART Channel Configuration, Data, and Status 77The HART data acquired by the auto acquisition process is copied to thepacket tags by using

Strany 163

78 ControlLogix™ Analog HART ModulesNote: The ladder in figure 7.6 can be found in the project sample filelocated on our website at (www.spectrumcont

Strany 164 - 150 ControlLogix

Chapter 7: HART Channel Configuration, Data, and Status 79Table 7.6 (Generic CIP Configuration)Unconnected Message Header Field Value Definition Mes

Strany 165

80 ControlLogix™ Analog HART ModulesGet HART Device InformationThe Get HART Device Information command is used to gather the devicespecific informatio

Strany 166 - 152 ControlLogix

Chapter 7: HART Channel Configuration, Data, and Status 81Table 7.9 (Response When Device Information Is Available)HART Get Device Information - reply

Strany 167 -

82 ControlLogix™ Analog HART Modules• Command and HART Channel number are both valid.• HART channel is enabled and communication has been established,

Strany 168 - 154 ControlLogix

Chapter 7: HART Channel Configuration, Data, and Status 83Note: If the resume command is received, without previously receiving asuspension command,

Strany 169 - Conformity

84 ControlLogix™ Analog HART Modulesignore the command and continue operation. This state of operationwill not be maintained after power-up or when c

Strany 170

Chapter 7: HART Channel Configuration, Data, and Status 85!Attention: If the HART message being sent orAttention: If the HART message being sent orA