10 Compact IO
Universal Input module
3. Wiring the module
4. Configuring the module
5. Going through the startup procedure
6. Monitoring module operation
Step 1: Ensure that your 1769 system
power supply(1) has sufficient current
output to support your system configuration. Reference
Chapter 3
(Installation and Wiring)
The modules maximum current draw is shown below
5V dc 24V dc
150 mA 45 mA
NOTE The module cannot be located more than 8 modules away from
the system power supply.
(1) The system power supply could be a 1769-PA2, -PB2, -PA4, -PB4, or the internal
supply of the MicroLogix 1500 packaged controller.
Step 2: Attach and lock the module. Reference
Chapter 3
(Installation and Wiring)
NOTE The module can be panel or DIN rail mounted. Modules can be
assembled before or after mounting.