B-6 Point IO™ 2/4 Channel Analog HART Module
User’s Manual Pub. 0300257-01 Rev. A
Command Data in Command Data in Reply Contained in
No.
Function Byte Data
Type
Byte Data
Type
Input
Tag
CIP
MSG
42 Perform
master reset
43 Set (trim)
PV zero
44 Write PV
units
0 PV units code As in command
45 Trim DAC
zero
0…3 Measured current
(mA)
46 Trim DAC
gain
0…3 (F)
47 Write
transfer
function
0 Transfer function
code
48 Read
additional
device
status
Moved to Universal
Commands in
HART version 7.
See 48 in Universal Commands
49 Write PV
sensor
serial
number
0…2 Sensor serial
number
As in command
50 Read
dynamic
variable
assignment
s
None 0
1
2
3
PV transmitter variable code
SV transmitter variable code
TV transmitter variable code
FV transmitter variable code
x
x
x
x
51 Write
dynamic
variable
assignment
s
0
1
2
3
PV transmitter
variable code
SV transmitter
variable code
TV transmitter
variable code
FV transmitter
variable code
As in command
52 Set
transmitter
variable
zero
0 Transmitter variable
code
53 Write
transmitter
variable
units
0
1
Transmitter variable
code
Transmitter var.
units code
54 Read
transmitter
variable
information
0 Transmitter variable
code
0
1…3
4
5…8
9…12
13…16
Transmitter variable code
Transmitter variable sensor serial
Transmitter var. limits units code
Transmitter variable upper limit
Transmitter variable lower limit
Transmitter var. damping value (sec)
(F)
(F)
(F)
55 Write
transmitter
variable
damping
value
0
1…4
Transmitter variable
code
Transmitter variable
damping value (sec)
(F)
As in command
56 Write
transmitter
variable
sensor
serial
number
0
1…3
Transmitter variable
code
Transmitter variable
sensor serial #
As in command
57 Read unit
tag,
description,
date
None 0…5
6…17
18…20
Unit tag
Unit descriptor
Unit date
(A)
(A)
(D)
x
x
x