18 PLC-5
TM
32-Channel Analog Input Module
Configuration Configuration
Configuration Configuration
Configuration
WW
WW
W
oror
oror
or
dd
dd
d
The channel configuration word is described below:
Input Type/Range must be configured using Binary or Hexidecimal values.
Word/Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Group
0 Channel 4 Channel 3 Channel 2 Channel 1 *Type/Range
1 Channel 8 Channel 7 Channel 6 Channel 5 *Type/Range
2 Channel 12 Channel 11 Channel 10 Channel 9 *Type/Range
3 Channel 16 Channel 15 Channel 14 Channel 13 *Type/Range
4 Channel 20 Channel 19 Channel 18 Channel 17 *Type/Range
5 Channel 24 Channel 23 Channel 22 Channel 21 *Type/Range
6 Channel 28 Channel 27 Channel 26 Channel 25 *Type/Range
7 Channel 32 Channel 31 Channel 30 Channel 29 *Type/Range
8 Channel 4 Channel 3 Channel 2 Channel 1 Data Format
9 Channel 8 Channel 7 Channel 6 Channel 5 Data Format
10 Channel 12 Channel 11 Channel 10 Channel 9 Data Format
11 Channel 16 Channel 15 Channel 14 Channel 13 Data Format
12 Channel 20 Channel 19 Channel 18 Channel 17 Data Format
13 Channel 24 Channel 23 Channel 22 Channel 21 Data Format
14 Channel 28 Channel 27 Channel 26 Channel 25 Data Format
15 Channel 32 Channel 31 Channel 30 Channel 29 Data Format
16 Chan 8 Chan 7 Chan 6 Chan 5 Chan 4 Chan 3 Chan 2 Chan 1 Filter Freq
17 Chan 16 Chan 15 Chan 14 Chan 13 Chan 12 Chan 11 Chan 10 Chan 9 Filter Freq
18 Chan 24 Chan 23 Chan 22 Chan 21 Chan 20 Chan 19 Chan 18 Chan 17 Filter Freq
19 Chan 32 Chan 31 Chan 30 Chan 29 Chan 28 Chan 27 Chan 26 Chan 25 Filter Freq
20 Automatic Calibration Rate Autocal
21 Debug Flags Debug Flags
22 Real Time Sampling RTS
Input Range SelectionInput Range Selection
Input Range SelectionInput Range Selection
Input Range Selection
Channels may be configured to acquire data as singled-ended inputs or as differential
pairs. During differential acquisition, odd channels (1, 3, 5, etc.) are the positive input
and the even channels (2, 4, 6, etc.) the negative inputs. A channel pair consists of
two consecutive channels (1&2, 3&4, 5&6, etc.). Within a channel pair both channels
must be specified as single acquisition or both as differential acquisition.
Word/Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Group
0 Channel 4 Channel 3 Channel 2 Channel 1 *Type/Range
1 Channel 8 Channel 7 Channel 6 Channel 5 *Type/Range
2 Channel 12 Channel 11 Channel 10 Channel 9 *Type/Range
3 Channel 16 Channel 15 Channel 14 Channel 13 *Type/Range
4 Channel 20 Channel 19 Channel 18 Channel 17 *Type/Range
5 Channel 24 Channel 23 Channel 22 Channel 21 *Type/Range
6 Channel 28 Channel 27 Channel 26 Channel 25 *Type/Range
7 Channel 32 Channel 31 Channel 30 Channel 29 *Type/Range
Several input ranges for voltage and current are supported. Ranges that include both
negative and positive values are referred to as bipolar ranges throughout this
document. Ranges that include only positive values are referred to as unipolar.
Within a group of 8 consecutive channels, all 8 channels must be from either 8
voltage or 8 current sources. If part of a voltage group, a channel may be any of the
allowed voltage ranges and if in a current group a channel may be any of the allowed
current ranges as long as all 8 are either voltage ranges or all 8 are current