Spectrum-controls 140 AUI 040 00sc Uživatelský manuál Strana 29

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 52
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 28
16-Channel Universal Analog Input Module
31
Chapter 5
INSTALLATION
+ Note: When field wiring the I/O modules, the maximum wire size that should be used is 1-14 AWG or 2-16 AWG; the
minimum size is 20 AWG.
+ Note: The field wiring terminal block (Modicon # 140 XTS 002 00) or the 140 CFA040 00 40 pin Cablefast
Terminal block must be ordered separately. (The terminal block includes the removable door label.)
+ Note: Power, input and output (I/O) wiring must be in accordance with Class 1, Division 2 wiring methods [Article
501-4 (b) of the National Electrical Code, NFPA 70] and in accordance with the authority having jurisdiction.”
+ Note: Peripheral equipment must be suitable for the location in which it is used.
Zobrazit stránku 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 51 52

Komentáře k této Příručce

Žádné komentáře